The Basic Requirements From a Generator Controller, When 2 or More Generators Run in Parallel

The Basic Requirements From a Generator Controller, When 2 or More Generators Run in Parallel

When two generators operate in parallel, their controllers must synchronise the generators, share the electrical load correctly, control the circuit breakers safely and protect the entire system.

1. Automatic synchronisation

Before the second generator connects to the live busbar, its controller must match:

  • Voltage
  • Frequency
  • Phase sequence
  • Phase angle

The controller adjusts the engine speed to match frequency and may control the AVR to match voltage. It must close the generator circuit breaker only when all synchronising conditions are within safe limits.

2. Active power (kW) load sharing

Once both generators are connected, the controllers must share the real power load between the engines.

Identical generators should normally share the kW load equally. Generators with different ratings should share it proportionally to their capacities. This is generally achieved by controlling the engine governors.

3. Reactive power (kVAr) load sharing

The controllers must also share the reactive load between the alternators. This affects:

  • Power factor
  • Alternator current
  • Reactive power in kVAr

Reactive load sharing is normally achieved by adjusting alternator excitation through the AVR. Poor kVAr sharing can overload one alternator even when the kW load appears to be shared correctly.

4. Generator circuit-breaker control

Each controller should be able to:

  • Open and close its generator circuit breaker
  • Confirm the breaker’s open and closed positions
  • Prevent unsafe or unsynchronised closing
  • Detect breaker failure or position disagreement
  • Trip the breaker following a serious fault

Reliable breaker auxiliary contacts are required to provide accurate position feedback.

5. Generator protection

The system should normally protect each generator against:

  • Overvoltage and undervoltage
  • Overfrequency and underfrequency
  • Overcurrent and short circuit
  • Reverse power
  • Overload
  • Loss of excitation
  • Excessive reactive power
  • Incorrect phase sequence
  • Failure to synchronise
  • Breaker failure
  • Low oil pressure
  • High coolant temperature
  • Engine overspeed

Reverse-power protection is particularly important because it prevents a generator from absorbing power and operating like a motor following a loss of engine power.

6. Busbar monitoring

The controllers must monitor the common busbar for:

  • Voltage
  • Frequency
  • Phase sequence
  • Live or dead busbar status
  • Permission to close

The system must also determine which generator is allowed to close first onto a dead busbar.

7. Automatic starting, stopping and sequencing

In automatic operation, the controllers should:

  • Start generators when power is required
  • Synchronise and connect the generators
  • Disconnect and stop an unnecessary generator when demand falls
  • Allow sufficient cooling time before shutdown
  • Rotate the lead generator to balance running hours

Start and stop settings should include suitable time delays to prevent repeated cycling when the load fluctuates.

8. Load-dependent start and stop

The system should always maintain sufficient generating capacity. For example, the second generator may start when the first reaches 70–80% load and stop when one generator can safely carry the total demand.

The settings should consider:

  • Sudden load changes
  • Motor starting requirements
  • The largest connected load
  • Required spinning reserve
  • Whether the system must tolerate the loss of one generator

9. Communication between controllers

The controllers normally require a reliable communication link to exchange information such as:

  • Generator availability
  • Breaker position
  • kW and kVAr loading
  • Start and stop priority
  • Load-sharing commands
  • System alarms

The design must also define how the system will respond if communication is lost. A communication failure must not cause unstable load sharing or unsafe breaker operation.

10. Load management

If the available generator capacity is insufficient, the controller or an external PLC should be able to:

  • Shed non-essential loads
  • Prevent additional loads from connecting
  • Restore loads in stages
  • Start another generator before accepting a large load

11. Operating modes

The system should provide clearly defined modes, including:

  • Manual
  • Automatic
  • Test
  • Maintenance or unavailable
  • Emergency stop

Manual operation should not allow essential synchronising and protection interlocks to be bypassed accidentally.

Summary

A suitable paralleling controller must perform four essential functions:

Synchronise the generators before connection

Share kW and kVAr correctly after connection

Control and interlock the generator circuit breakers

Protect the generators and manage system operation

A controller designed only for automatic starting and stopping is not necessarily suitable for parallel operation. It must specifically support generator-to-generator synchronisation, active and reactive load sharing, breaker control and system sequencing.

29 Jul 2026

Chat with us on whatsapp